Rectifier module
Type GR-5713 (1~) and GR-5701 (3~)
The modules can be used with or without an external buffer battery.
Scope of application
Our rectifier modules are used in system cabinets. They are usually used as power supply units for industrial applications or as rectifiers with buffer batteries.
The rectifier modules can be extended with further module solutions to individual and customised power supplies (e.g. several voltage levels by means of DC converters, AC supply by means of inverters).
The modules can be operated without an additional controller, which reduces dependency on a central module as well as operating costs (no software updates required, fewer potential failures).
Special features
- Primary clocked technology
- Modules can be connected in parallel
- Easily accessible connection (replacement possible during operation)
- Partially with integrated decoupling diode
- Predominantly fanless design
- Interfaces and displays: LED, test sockets, potential-free changeover contact (operation/fault)
State of the art
- Inrush current to max. 1.2 x IN limited
High test voltages:
– Input-output 5.3 kV DC
– Input body 2.8 kV DC
– Output body 2.8 kV DC - Design according to current standards
- Design life and spare parts guarantee: 15 years
Options
- Temperature controlled charge
- Additional controller, e.g. for digital display, for integration of further interfaces
Technical data
Type GR-5713 (1~) and GR-5701 (3~)
Mains voltage | 1/N/PE AC 230 V 3/PE AC 400/230 V |
Frequency | 45 – 63 Hz |
Power factor cos phi | > 0.95 (10 - 100 % load) |
Crest factor | < 1,6 |
Voltage characteristics | 2.0 / 2.23 / 2.4 (adjustable) V / Z |
Accuracy of the | ± 1 % |
Control response time | 10 ms |
Output voltage tolerance | < 2 % |
Current limitation | at rated current |
Control characteristic | IU charge acc. EN IEC 62485-2 |
Output voltage ripple | ≤ 1 % eff. |
Interference voltage | < 1 mV (24 V); < 2 mV (48/60 V) frequency-weighted (CCITT-A-filter) |
EMC | according to EN 61000-6-2 and EN 61000-6-4 |
Protection class acc. EN 60529 | IP 20 |
Permissible environmental conditions: Storage according to EN 60721-3-1 Transport according to EN 60721-3-2 Operation according to EN 60721-3-3 | 1K21 / 1M11 +5 to +40 °C 2K12 / 2M4 -45 to +70 °C 3K22 / 3M11 +5 to +40 °C
|
Standard types
Input voltage V | Output voltage V | Output current A | Dimension B x H x D in mm | Cooling 1) | Weight in kg | 230 | 24/26 | 25 | 88 x 304 x 352 | AN | 3,8 |
---|---|---|---|---|---|
230 | 24 | 25 | 88 x 304 x 352 | AN | 3,8 |
230 | 60 | 10 | 88 x 304 x 352 | AN | 3,8 |
230 | 110 | 35 | 483 x 265,9 x 444 | AF | 33 |
230 | 220 | 35 | 483 x 265,9 x 444 | AF | 33 |
230 | 48/60 | 25 | 132 x 355 x 440 | AN | 7,4 |
230 | 62/68,1 | 10 | 88 x 304 x 352 | AN | 3,8 |
400 | 12 | 50 | 132 x 355 x 442 | AN | 9,0 |
400 | 24 | 50 | 132 x 304 x 442 | AN | 9,0 |
400 | 24 | 100 | 150 x 449 x 303 | AN | 14,0 |
400 | 110 | 30 | 180 x 449 x 442 | AN | 16,0 |
400 | 62/67, 67/72 | 25 | 110 x 304 x 382 | AN | 6,3 |
400 | 36 | 50 | 180 x 449 x 442 | AN | 16 |
230 | 62 / 67, 67 / 72 | 25 | 132 x 355 x 442 | AN | 7,4 |
400 | 110 | 12,5 | 110 x 304 x 382 | AN | 6,3 |
400 | 110 | 30 | 132 x 355 x 442 | AF | 9,4 |
400 | 110 | 100 | 483 x 265,9 x 444 | AF | 40 |
400 | 62/67, 67/72 | 50 | 132 x 355 x 442 | AF | 9,4 |
400 | 62/67, 67/72 | 50 | 180 x 449 x 442 | AN | 16 |
Other versions on request
1) „AN“ natural cooling; „AF“ forced air self-cooling (fan)
Subject to technical changes
We will be happy to check your requirements/
Learn more!
You want to know more about our products? We will be happy to send you more information by e-mail!