DC power supply / fanless / railway approval

DC converters

Primary clocked DC converter modules are used, among other things, to generate different (consumer) voltage levels from central DC voltages, also battery-supported.

Scope of application

Primary clocked DC converter modules are used, among other things, to generate different (consumer) voltage levels from central DC voltages, also battery-supported.
Our clocked DC converter modules for use in the low-voltage range can be connected in parallel in any quantity to increase power and redundancy.
The units are designed as plug-in modules for cabinet installation and offer galvanic isolation between input and output.

The connections on the front allow easy exchange of the modules.
As a special form, we offer DC converters without galvanic isolation on request for adapting e.g. specific battery voltage ranges to specified consumer voltages (function: e.g. “step-up converter”).

Due to their design, our modules are ideally suited for a wide range of industrial applications.

Essential features

  • Galvanic isolation between input and output
  • High efficiencies
  • Parallel switchable without additional control unit
  • Compact design with easily accessible connections on the front side
  • Fanless design (low noise, no fan replacement necessary)
  • High test voltages acc. EN 50124-1 from the railway sector
    Module-specific:
    • Integrated decoupling diode
    • 2 x IN Short-circuit current, limited to 1.2 to 1.5 s
    • Relay interface with potential-free changeover contact (operation / fault)
    • Signalling by means of LEDs, partly digital voltmeter

Technical data

DCW-5751

Nominal data

DC input voltage tolerance

-15 % to +20
-15 % to +20

Input and output voltage

Module-specific

Voltage tolerance

± 1 %

Output ripple

Module-specific, < 0,5 … 1 % eff.

Safety, environmental conditions, execution

Protection class according to EN 61140

1

Protection class according to EN 60529

IP 20

Permissible environmental conditions:

Storage according to EN 60721-3-1

1K21 / 1M11 +5 to +40 °C

Transport according to EN 60721-3-2

2K12 / 2M4 -45 to +70 °C

Operation according to EN 60721-3-3

3K22 / 3M11 +5 to +40 °C

  • 5-85 % rel. Humidity, no condensation
  • Pollution degree 2

Permissible installation height at nominal load

1,000 m above sea level
Minimum air pressure 870 hPa

Installation site

Cabinet installation

Connection

Front

Housing

Installation housing sheet steel / anodised front panel

Cooling type

"AN" natural cooling (fanless)

High-voltage test

Test voltages

  • primary / secondary, signals: 5.3 kVDC
  • Signals / secondary: 5.3 kVDC
  • primary / body: 2.8 kVDC
  • secondary / body: 2.8 kVDC
  • Signals / body: 2.8 kVDC

General data

Current limitation

at rated current

Overload/short circuit behaviour

short-circuit proof, increased current limitation
module-specific

Parallel connection

without limitation of the number

Operating mode

Continuous operation

Applied guidelines and standards

Low Voltage Directive

2014/35/EU

EMC Directive

2014/30/EU

RoHS Directive

2011/65/EU

EMC standards

EN 50121-4
EN 55011
EN IEC 61000-6-2
EN IEC 61000-6-4
EN IEC 61204-3

General requirements
and safety requirements

EN 50124-1
EN 60529
EN 60721-x
EN 61140
EN IEC 61204-7
EN IEC 63000

Detailed, module-specific data on request or see product brochure.
Subject to technical changes

We will be happy to check your requirements/specification for feasibility.

Brochure as PDF