DC power supply / fanless / railway approval
DC converters
Primary clocked DC converter modules are used, among other things, to generate different (consumer) voltage levels from central DC voltages, also battery-supported.

Scope of application
Primary clocked DC converter modules are used, among other things, to generate different (consumer) voltage levels from central DC voltages, also battery-supported.
Our clocked DC converter modules for use in the low-voltage range can be connected in parallel in any quantity to increase power and redundancy.
The units are designed as plug-in modules for cabinet installation and offer galvanic isolation between input and output.
The connections on the front allow easy exchange of the modules.
As a special form, we offer DC converters without galvanic isolation on request for adapting e.g. specific battery voltage ranges to specified consumer voltages (function: e.g. “step-up converter”).
Due to their design, our modules are ideally suited for a wide range of industrial applications.
Essential features
- Galvanic isolation between input and output
- High efficiencies
- Parallel switchable without additional control unit
- Compact design with easily accessible connections on the front side
- Fanless design (low noise, no fan replacement necessary)
- High test voltages acc. EN 50124-1 from the railway sector
Module-specific:- Integrated decoupling diode
- 2 x IN Short-circuit current, limited to 1.2 to 1.5 s
- Relay interface with potential-free changeover contact (operation / fault)
- Signalling by means of LEDs, partly digital voltmeter
Technical data
DCW-5751
Nominal data
DC input voltage tolerance |
-15 % to +20 |
Input and output voltage |
Module-specific |
Voltage tolerance |
± 1 % |
Output ripple |
Module-specific, < 0,5 … 1 % eff. |
Safety, environmental conditions, execution
Protection class according to EN 61140 |
1 |
Protection class according to EN 60529 |
IP 20 |
Permissible environmental conditions:
Storage according to EN 60721-3-1 |
1K21 / 1M11 +5 to +40 °C |
Transport according to EN 60721-3-2 |
2K12 / 2M4 -45 to +70 °C |
Operation according to EN 60721-3-3 |
3K22 / 3M11 +5 to +40 °C
|
Permissible installation height at nominal load |
1,000 m above sea level |
Installation site |
Cabinet installation |
Connection |
Front |
Housing |
Installation housing sheet steel / anodised front panel |
Cooling type |
"AN" natural cooling (fanless) |
High-voltage test |
Test voltages
|
General data
Current limitation |
at rated current |
Overload/short circuit behaviour |
short-circuit proof, increased current limitation |
Parallel connection |
without limitation of the number |
Operating mode |
Continuous operation |
Applied guidelines and standards
Low Voltage Directive |
2014/35/EU |
EMC Directive |
2014/30/EU |
RoHS Directive |
2011/65/EU |
EMC standards |
EN 50121-4 |
General requirements |
EN 50124-1 |
Detailed, module-specific data on request or see product brochure.
Subject to technical changes
We will be happy to check your requirements/
Brochure as PDF
Learn more!