UPS / secured regenerative power supply / railway approval

Industry UPS systems

Type UPS-7011 (1~)
Type USV-7013 (3~)

Rated power up to 200 kVA 1~
up to 500 kVA 3~

BSV-Anlagen

Scope of application

Our static uninterruptible power supply (UPS) systems comply with the VFI-SS-11 classification according to IEC 62040-3.

With their robust industrial design, they support a secure consumer supply in continuous operation. In times of energy transition, our UPS systems protect against system failures caused by interruptions and disturbances in the grid feed.

Customers from the telecom, railroad, power generation / distribution, chemical industry, among others, have been relying on the high quality and reliability of our UPS systems for decades.

Essential features

Gustav Klein UPS systems are equipped with a colour touch screen display and consist of the components:

  • IGBT rectifier (regenerative) with isolation transformer
  • Battery (energy storage)
  • IGBT inverter in PWM technology with galvanic isolation at the output
  • Electronic bypass
  • Manual bypass

Features and advantages

  • Highest availability and long service life
  • Spare parts delivery for at least 15 years
  • Efficient and cost-effective maintenance and servicing due to well thought-out unit design
  • Fanless UPS design for smaller outputs
  • Interruption time 0 ms
  • Compatible with various battery types (including lead closed or sealed, NiCd)
  • Direct display and intuitive operation via color TFT display (including event ring memory, password-protected user levels)
  • Supports consumption-optimized networks (input THDi ≤ 6%, hardly any reactive power consumption, battery test by means of mains regeneration and full UPS power).
  • High performances available:
    single-phase up to 200 kVA, three-phase up to 500 kVA
  • Many custom options available

Options (excerpt)

  • Mains/output voltage deviating from 400 V AC
  • Battery voltage DC link 110 V DC, 220 V DC or 372 V DC
  • Battery rack, battery cabinet
  • Battery cabinet fan with fan monitoring
  • Earth fault monitoring
  • Integration distribution
  • Isolating transformer acc. VDE 0558-507 or ÖVE / ÖNORM E 8007 in bypass cabinet
  • Parallel running device
  • Large selection of interfaces available (e.g. SNMP, Modbus)
  • separate bypass cabinet
  • increased/specific short-circuit currents
  • Optionally, our UPS systems are also available based on thyristor technology (USV-7001 1~ or USV-7003 3~).

Technical data

UPS system
Type UPS-7011 and UPS-7013

Nominal power

10-200 kVA 1~
10-500 kVA 3~

Rectifiers

Mains voltage

3/N/PE AC 400/230 V ± 10 %
Other voltages can be realised.

Frequency

50 or 60 Hz ± 5 %

Power factor at nominal power

>0,99

Rated output voltage

110 / 220 / 372 V DC

Bypass

Input voltage

1/N/PE AC 230 V or
3/N/PE AC 400/230 V

Frequency

50 Hz ± 5 %

Overload capacity for 10 ms

10 x IN

Inverter / UPS output

Current feedback effects on
the DC rail

≤ 10 %eff IN

Output voltage

1/N/PE AC 230 V or 3/N/PE AC 400/230 V

Voltage tolerance

static

± 1 %

dynamic

± 4 % @ 100 % load change

asymmetrical load

± 2 % @ 100 % unbalance L-N

Output voltage setting range

± 5 %

Settling time (instantaneous value control)

< 4 ms

Waveform

sinusoidal

Distortion factor (with linear load)

≤ 3 %

Frequency

50 or 60 Hz ± 0.1 % or
mains-synchronised to the AC input

Synchronisation range

± 3 %

Frequency change rate

1 Hz/s

Overload behaviour

1.50 x INom for 60 seconds
1.25 x INom for 10 minutes
1.10 x INom for 20 minutes

Short-circuit behaviour

Short circuit proof,

Short-circuit current 2 x INom (1-phase)

Short-circuit current 2-4 x INom (3-phase)

Inverter stop after 5 s

Permissible power factor

0.0 inductive - 0.0 capacitive
Power reduction in case of deviation from cos φ 0.8 ind.

Permissible crest factor of the load current

≤ 2.3 at rated power

General data

Protection class according to EN 60529

IP 20 (floor IP00)

Permissible installation height at nominal load

1,000 m above sea level
Minimum air pressure 870 hPa

Paintwork

RAL 7035 solid colour textured lacquer

Cooling type

"AN" natural cooling or
„AF“ forced air cooling

Applied guidelines and standards

Low Voltage Directive

2014/35/EU

Permissible environmental conditions:

Storage according to EN 60721-3-1

1K21 / 1M11 +5 to +40 °C

Transport according to EN 60721-3-2

2K12 / 2M4 -45 to +70 °C

Operation according to EN 60721-3-3

3K22 / 3M11 +5 to +40 °C

  • 5-85 % rel. Humidity, no condensation
  • Pollution degree 2

EMC Directive

2014/30/EU

RoHS Directive

2011/65/EU

EMC standards

EN 61439-1
EN 61439-2
EN IEC 62040-2

General requirements
and safety requirements

EN 61439-1
EN 61439-2
EN 60721-x
EN IEC 62040-1
EN 62040-3
EN 62477-1
EN IEC 63000

Subject to technical changes

We will be happy to check your requirements/specification for feasibility.

Brochure as PDF

Learn more!

You want to know more about our products? We will be happy to send you more information by e-mail!