Rectifier module

Type GR-5713 (1~) and GR-5701 (3~)

System components for DC supplies with / without backup battery.

Scope of application

Our rectifier modules are used in system cabinets for industrial applications.
In addition to pure stand-alone operation, individual and customer-specific power supplies can be realized by means of additional components, e.g:
– Redundant DC supplies (100%, n+1 redundancy, etc.)
– Fused DC power supplies with battery
– Various DC voltage levels with downstream DC converters
– AC/DC supplies with downstream inverters
The possibility of operating the modules without an additional controller helps to increase system availability (no dependency on a central module) and reduce operating costs (no software updates required, fewer potential malfunctions).

Special features

  • Primary clocked technology
  • Operating mode: Continuous operation
  • short-circuit proof
  • Modules can be connected in parallel
  • Partly with integrated decoupling diode
  • Easily accessible connections on the front (can be replaced during operation)
  • Predominantly fanless design
  • Interfaces and displays: LED, test sockets, potential-free changeover contact (operation/fault)

State of the art

  • High-quality and tested design for industrial applications, including
    – Design in accordance with current relevant standards
    – High test voltages
    – Inrush current limited
  • Sustainability is ensured, among other things, by a design service life and a spare parts guarantee of 15 years

Options

  • Individual functionalities for operation with batteries (charging characteristics, temperature control, symmetry monitoring, …)
  • Additional controller, e.g. for digital display, for integration of further interfaces

Technical data

Type GR-5713 (1~) and GR-5701 (3~)

Mains voltage

1/N/PE AC 230 V or

3/PE AC 400/230 V

Frequency

50 Hz (range: 45 - 63 Hz) or variants with 16.7 Hz

Voltage level (battery)

e.g. 2.0 / 2.23 / 2.4 (adjustable) V / cell

Accuracy of the
Output voltage

± 1 %

Current limitation

at rated current

Charging characteristics

IU charge acc. EN IEC 62485-2

Output voltage ripple

≤ 1 % eff.

EMC

according to EN 61000-6-2 and EN 61000-6-4 and EN 50121-4

Protection class acc. EN 60529

IP 20

Protection class acc. EN61140:

1

Permissible environmental conditions:

Storage according to EN 60721-3-1

Transport according to EN 60721-3-2

Operation according to EN 60721-3-3

1K21 / 1M11 +5 to +40 °C

2K12 / 2M4 -45 to +70 °C

3K22 / 3M11 +5 to +40 °C

  • 5-85 % rel. Humidity, no condensation
  • Pollution degree 2

Test voltages:

  • Input-output 5,3 kV DC
  • Input body 2,8 kV DC
  • Output body 2,8 kV DC

Standard types

Input voltage V
Input frequency Hz
Output voltage V
Output current A
Dimensions Width x Depth x Height in mm
Cooling type 1)

230

50

24

25

88 x 352 x 304

AN

230

50

48 (60)

10

88 x 352 x 304

AN

230

50

48 (60)

25

132 x 442 x 355

AN

230

16,7

24

25

88 x 352 x 304

AN

230

16,7

48 (60)

10

88 x 352 x 304

AN

230

16,7

48 (60)

25

132 x 440 x 355

AN

400

50

24

50

132 x 442 x 304

AN

400

50

24

100

150 x 303 x 449

AN

400

50

48 (60)

25

110 x 382 x 304

AN

400

50

48 (60)

50

180 x 442 x 449

AN

400

50

48 (60)

50

132 x 442 x 335

AF

400

50

110

12,5

110 x 382 x 304

AN

400

50

110

30

180 x 442 x 449

AN

400

50

110

30

132 x 442 x 355

AF

400

50

110

100

483 x 444 x 265,9

AF

400

50

220

30

267 x 442 x 355

AF

400

50

220

50

483 x 444 x 265,9

AF

Other versions (e.g. 12 / 36 V) on request
1) „AN“ natural cooling; „AF“ forced air self-cooling (fan)

Subject to technical changes

We will be happy to check your requirements/specification for feasibility

Learn more!

You want to know more about our products? We will be happy to send you more information by e-mail!