Rectifier module

Type GR-5713 (1~) and GR-5701 (3~)

The modules can be used with or without an external buffer battery.

Scope of application

Our rectifier modules are used in system cabinets. They are usually used as power supply units for industrial applications or as rectifiers with buffer batteries.
The rectifier modules can be extended with further module solutions to individual and customised power supplies (e.g. several voltage levels by means of DC converters, AC supply by means of inverters).
The modules can be operated without an additional controller, which reduces dependency on a central module as well as operating costs (no software updates required, fewer potential failures).

Special features

  • Primary clocked technology
  • Modules can be connected in parallel
  • Easily accessible connection (replacement possible during operation)
  • Partially with integrated decoupling diode
  • Predominantly fanless design
  • Interfaces and displays: LED, test sockets, potential-free changeover contact (operation/fault)

State of the art

  • Inrush current to max. 1.2 x IN limited
    High test voltages:
    – Input-output 5.3 kV DC
    – Input body 2.8 kV DC
    – Output body 2.8 kV DC
  • Design according to current standards
  • Design life and spare parts guarantee: 15 years

Options

  • Temperature controlled charge
  • Additional controller, e.g. for digital display, for integration of further interfaces

Technical data

Type GR-5713 (1~) and GR-5701 (3~)

Mains voltage

1/N/PE AC 230 V

3/PE AC 400/230 V

Frequency

45 – 63 Hz

Power factor cos phi

> 0.95 (10 - 100 % load)

Crest factor

< 1,6

Voltage characteristics

2.0 / 2.23 / 2.4 (adjustable) V / Z

Accuracy of the
Output voltage

± 1 %

Control response time

10 ms

Output voltage tolerance
at load step 10-100-10 %

< 2 %

Current limitation

at rated current

Control characteristic

IU charge acc. EN IEC 62485-2

Output voltage ripple

≤ 1 % eff.

Interference voltage

< 1 mV (24 V); < 2 mV (48/60 V) frequency-weighted (CCITT-A-filter)

EMC

according to EN 61000-6-2 and EN 61000-6-4

Protection class acc. EN 60529

IP 20

Permissible environmental conditions:

Storage according to EN 60721-3-1

Transport according to EN 60721-3-2

Operation according to EN 60721-3-3

1K21 / 1M11 +5 to +40 °C

2K12 / 2M4 -45 to +70 °C

3K22 / 3M11 +5 to +40 °C

  • 5-85 % rel. Humidity, no condensation
  • Pollution degree 2

Standard types

Input voltage V
Output voltage V
Output current A
Dimension B x H x D in mm
Cooling 1)
Weight in kg

230

24/26

25

88 x 304 x 352

AN

3,8

230

24

25

88 x 304 x 352

AN

3,8

230

60

10

88 x 304 x 352

AN

3,8

230

110

35

483 x 265,9 x 444

AF

33

230

220

35

483 x 265,9 x 444

AF

33

230

48/60

25

132 x 355 x 440

AN

7,4

230

62/68,1

10

88 x 304 x 352

AN

3,8

400

12

50

132 x 355 x 442

AN

9,0

400

24

50

132 x 304 x 442

AN

9,0

400

24

100

150 x 449 x 303

AN

14,0

400

110

30

180 x 449 x 442

AN

16,0

400

62/67, 67/72

25

110 x 304 x 382

AN

6,3

400

36

50

180 x 449 x 442

AN

16

230

62 / 67, 67 / 72

25

132 x 355 x 442

AN

7,4

400

110

12,5

110 x 304 x 382

AN

6,3

400

110

30

132 x 355 x 442

AF

9,4

400

110

100

483 x 265,9 x 444

AF

40

400

62/67, 67/72

50

132 x 355 x 442

AF

9,4

400

62/67, 67/72

50

180 x 449 x 442

AN

16

Other versions on request
1) „AN“ natural cooling; „AF“ forced air self-cooling (fan)

Subject to technical changes