Thyristor Rectifiers
GR-3811 with touch screen TFT display
GR-3812 with LC-Display

Equipment
- Thyristor rectifier 6-pulse (12-pulse optional)
- Input contactor for rectifier
- Automatic charge
- Analogue control
- Microprocessor-controlled monitoring
- Digital display with event ring memory (non-volatile):
– GR-3811: colour TFT panel with touch screen
– GR-3812: LC display with LED indicators in mimic diagram - Power unit with two-stage temperature monitoring
(Warning message / shutdown) - Galvanic isolation between input and output
- 8 remote signals (potential-free contacts, configurable)
- RS232 interface
- Can be connected in parallel
- Programmable battery test
State of the art
- User-friendly, intuitive operation
- 3 Charging characteristics IU (automatic)
- Fanless design (natural air cooling by convection)
- Design according to current standards
Our options (excerpt)
- Specific electrical parameters, e.g. frequency / voltage
- Specific mechanical parameters, e.g. protection class (IP21 and higher), base plate
- Equipment and functionalities, e.g.: Protective devices (MCCB, surge arrester …), monitoring (fan, earth fault …), interfaces (Profibus, Modbus, SNMP …), temperature-controlled battery charging …
- More on request
Technical data
GR-3811 and GR-3812
Rated voltage | 24 / 48 / 60 / 110 / 120 / 220 |
Rated current | Up to 1500 A |
Rectifier version | Galvanically isolated, thyristor 6-pulse, |
Input voltage | 3/N/PE AC 400/230 V +/-10% |
Voltage tolerance (output) | ±1 % |
Frequency | 50 Hz ±5 % |
Charging code | IU charge acc. DIN 41772 3 |
Voltage ripple | <2% eff. without battery |
Security | 1 acc. EN 60950-1 |
Protective conductor current | < 5 % INom typ. 50 mA |
Protection class | IP 20 (floor IP00) according to EN 60529 |
Permissible installation altitude | 1000 m above sea level |
Installation site |
|
Connection | front, bottom - accessible after opening the door |
Display and control unit | GR-3811: Color TFT - panel with touch screen display GR-3812: LC-Display |
Remote signalling | 8 signals / 2 potential-free change-over contacts per signal
|
Test voltage |
|
Applied guidelines and standards
Low Voltage Directive | 2014/35/EU |
EMC Directive | 2014/30/EU |
RoHS Directive | 2011/65/EU |
Permissible environmental conditions:
Storage according to EN 60721-3-1 | 1K21 / 1M11 +5 to +40 °C |
Transport according to EN 60721-3-2 | 2K12 / 2M4 -45 to +70 °C |
Operation according to EN 60721-3-3 | 3K22 / 3M11 +5 to +40 °C
|
Depending on configuration, subject to change
We will be happy to check your requirements/
Brochure as PDF
Learn more!
You want to know more about our products? We will be happy to send you more information by e-mail!