Mains simulation / Bidirectional

AC source/sink

AC source/sink (option)
Type TS-AC-5445(1~) / RTS-AC-5445(1~)
Type TS-AC-5446(3~) / RTS-AC-5446(3~)

Adjustable AC source/sink
Rated power up to 200kVA 1~, up to 500kVA 3~

Frequencies from 16.7 to 800 Hz

Version

The static AC source contains tried and tested components of our UPS technology.
Available with adjustable output frequency and / or output voltage.
Clear design, tried and tested components and easy maintenance are the distinguishing features of this AC source.

Features

Options

Technical data

AC source type (R)TS-AC-5445 and (R)TS-AC-5446

Mains voltage

208/380/400/440/480/500/660/690 V (3~, PE)
+/- 10 %
16,7 Hz, 50 Hz or 60 Hz

Output voltage

10 - 600 V ±1 % fixed or adjustable
(other ranges on request)
1- or 3-phase

Output frequency range

45-105, 195-805, 95-420 Hz
(other ranges on request)

Output frequency accuracy

±0,1 % fs

Nominal power

10 – 500 kVA

Voltage tolerance

static: ±1 % (of final value)
dynamic: ±4 % at 100 % load change (< 400 Hz),
±8 % (400/800 Hz)
asymmetrical load: ±2 % at 100 % unbalanced load (L-N)

Settling time RMS value

< 25 ms

Settling time instantaneous value

< 4 ms

Overload behaviour

150 % for 1 min. / 125 % for 10 min. /
110 % for 20 min.

Short-circuit behaviour

2 x INom (1-phase),
2-4 x INom (3-phase),
Inverter stop after 5 s

Waveform

sinusoidal

Distortion factor

≤ 3 % ꟾ at > 100 Hz ≤ 5 %

Applied guidelines and standards

Low Voltage Directive

2014/35/EU

EMC Directive

2014/30/EU

RoHS Directive

2011/65/EU

EMC behaviour

EN 62040-2 EMC requirements (UPS)
EN 61000-6-2 Noise immunity
EN 6100-6-4 Emitted interference

Permissible power factor

arbitrary, power reduction
with deviation of 0.8 ind.

Permissible crest factor of the load current

≤ 2.3 (at 100% load)

General data

Permissible environmental conditions:

Storage according to EN 60721-3-1

1K21 / 1M11 +5 to +40 °C

Transport according to EN 60721-3-2

2K12 / 2M4 -45 to +70 °C

Operation according to EN 60721-3-3

3K22 / 3M11 +5 to +40 °C

  • 5-85 % rel. Humidity, no condensation
  • Pollution degree 2

Permissible installation altitude

1000 m above sea level at nominal load

Protection class

IP 20 according to IEC 60529

Paintwork

RAL 7035

Cooling type

"AN" natural cooling or
"AF" reinforced cooling
depending on output

Depending on configuration, subject to change

We will be happy to check your requirements/specification for feasibility.